Fire Detection Devices CF-200-EWT is a fixed temperature only detector. The fixed temperature portion releases when the ceiling temperature reaches 200°F (93°C). Spacing is 25 ft. (7.6m). The CF-200EWT identified by a black dot and a white dot on the heat collector fin.
A cast aluminum housing encloses a standard Thermoflex® heat detector making it suitable for use in hazardous locations including those requiring detectors that are explosion proof, water and also dust tight.
The Thermoflex product group includes standard detectors as well as detectors for hazardous locations and moisture-proof applications. Each detector is available in single or multiple circuits with open and/or closed contact configurations. The prefix CR in the model number denotes rate-or-rise and fixed temperature operation. The prefix CF denotes fixed temperatures only. The standard fixed temperature settings are 135°F and 200°F. Units set at 165°F and 285°F are also available.
Fire Detection Devices CF-200-EWT must be install in areas where corrosive elements exist or washing of walls and also ceiling surfaces is commonplace. The fixed temperature portion and the rate-of-rise operation determined by the ambient temperature. Additionally, Thermoflex® A-type detectors shall be installed in areas where environmental conditions including dust, vapors, insects, etc., would cause an ionization or photoelectric type detector to initiate a false alarm.